How Much to Add for Roof Pitch

A footprint measured from the ground or a plan is flat. The roof is not. Multiply by the pitch factor to get the real surface you have to cover.

Add for pitch calculator

Include the overhangs

The pitch multiplier

Sloped area = flat area × multiplier Multiplier = √(pitch² + 144) ÷ 12 Add for pitch (%) = (multiplier − 1) × 100

The multiplier is the length of a rafter for each foot of level run. Because every plane of a roof with one pitch tilts by the same amount, it works for gable, hip and most combination roofs alike: measure the outside footprint including overhangs, then multiply once. Roofs with mixed pitches need each section handled separately, which the measure a roof guide covers.

Pitch factor table

The table also gives each pitch in degrees, since many apps, saws and solar specs ask for the angle. For example, a 2/12 pitch is 9.46°, a 3/12 pitch is 14.04° and a 20/12 pitch is 59.04°. The pitch to degrees converter handles any value, including fractions like 2.5/12.

Pitch factor and angle for 1/12 to 24/12
PitchDegreesMultiplierAdd for pitch1,000 sq ft footprint becomes
1/124.76°1.00350.3%1,003 sq ft
2/129.46°1.01381.4%1,014 sq ft
3/1214.04°1.03083.1%1,031 sq ft
4/1218.43°1.05415.4%1,054 sq ft
5/1222.62°1.08338.3%1,083 sq ft
6/1226.57°1.118011.8%1,118 sq ft
7/1230.26°1.157715.8%1,158 sq ft
8/1233.69°1.201920.2%1,202 sq ft
9/1236.87°1.250025.0%1,250 sq ft
10/1239.81°1.301730.2%1,302 sq ft
11/1242.51°1.356635.7%1,357 sq ft
12/1245.00°1.414241.4%1,414 sq ft
13/1247.29°1.474347.4%1,474 sq ft
14/1249.40°1.536653.7%1,537 sq ft
15/1251.34°1.600860.1%1,601 sq ft
16/1253.13°1.666766.7%1,667 sq ft
17/1254.78°1.734173.4%1,734 sq ft
18/1256.31°1.802880.3%1,803 sq ft
19/1257.72°1.872787.3%1,873 sq ft
20/1259.04°1.943794.4%1,944 sq ft
21/1260.26°2.0156101.6%2,016 sq ft
22/1261.39°2.0883108.8%2,088 sq ft
23/1262.45°2.1619116.2%2,162 sq ft
24/1263.43°2.2361123.6%2,236 sq ft

Worked examples

Ranch house, 4/12. Footprint 60 × 30 ft with 1 ft overhangs: 62 × 32 = 1,984 sq ft. × 1.0541 = 2,091 sq ft, or 20.9 squares. The pitch adds only 107 sq ft.
Two-story colonial, 9/12. Footprint 40 × 28 with overhangs: 42 × 30 = 1,260 sq ft. × 1.25 = 1,575 sq ft. The pitch adds a full quarter.
Rafter length. The same multiplier converts horizontal run to sloped length. A 13 ft run at 8/12 is 13 × 1.2019 = 15.62 ft along the slope, before the overhang.

Half-pitch multipliers and material limits

Pitches like 2.5/12 and 4.5/12 are common on additions and porches. Here is every half step, with the OSHA roof class and the pitch where each covering becomes code-legal.

Every roof pitch from 0.5/12 to 12/12: angle, multiplier, OSHA class and the coverings it allows
PitchDegreesSlope %Area multiplierRoof classCode minimum reached (IRC R905)
0.5/122.39°4.2%1.0009Low-slope (OSHA)Now allowed: Standing-seam metal panels; Built-up, modified bitumen, single-ply membrane; Lapped metal panels with lap sealant
1/124.76°8.3%1.0035Low-slope (OSHA)Now allowed: Mineral-surfaced roll roofing
1.5/127.13°12.5%1.0078Low-slope (OSHA)
2/129.46°16.7%1.0138Low-slope (OSHA)Now allowed: Asphalt shingles
2.5/1211.77°20.8%1.0215Low-slope (OSHA)Now allowed: Clay and concrete tile
3/1214.04°25.0%1.0308Low-slope (OSHA)Now allowed: Metal roof shingles; Lapped metal panels, no sealant; Wood shingles and shakes
3.5/1216.26°29.2%1.0417Low-slope (OSHA)
4/1218.43°33.3%1.0541Low-slope (OSHA)Now allowed: Slate
4.5/1220.56°37.5%1.0680Steep roof (OSHA)
5/1222.62°41.7%1.0833Steep roof (OSHA)
5.5/1224.62°45.8%1.1000Steep roof (OSHA)
6/1226.57°50.0%1.1180Steep roof (OSHA)
6.5/1228.44°54.2%1.1373Steep roof (OSHA)
7/1230.26°58.3%1.1577Steep roof (OSHA)
7.5/1232.01°62.5%1.1792Steep roof (OSHA)
8/1233.69°66.7%1.2019Steep roof (OSHA)
8.5/1235.31°70.8%1.2255Steep roof (OSHA)
9/1236.87°75.0%1.2500Steep roof (OSHA)
9.5/1238.37°79.2%1.2754Steep roof (OSHA)
10/1239.81°83.3%1.3017Steep roof (OSHA)
10.5/1241.19°87.5%1.3288Steep roof (OSHA)
11/1242.51°91.7%1.3566Steep roof (OSHA)
11.5/1243.78°95.8%1.3851Steep roof (OSHA)
12/1245.00°100.0%1.4142Steep roof (OSHA)

Minimum roof pitch by material

Minimum roof pitch by material (International Residential Code)
Roof coveringMinimum pitchDegreesIRC sectionNote
Standing-seam metal panels0.25/121.19°R905.10.2—
Built-up, modified bitumen, single-ply membrane (TPO, EPDM, PVC)0.25/121.19°R905.9, R905.11, R905.12Design slope for drainage
Lapped metal panels with lap sealant0.5/122.39°R905.10.2—
Mineral-surfaced roll roofing1/124.76°R905.5.2—
Asphalt shingles2/129.46°R905.2.2Double underlayment from 2/12 up to 4/12
Clay and concrete tile2.5/1211.77°R905.3.2Double underlayment from 2.5/12 up to 4/12
Metal roof shingles3/1214.04°R905.4.2—
Lapped metal panels, no sealant (exposed-fastener)3/1214.04°R905.10.2—
Wood shingles and shakes3/1214.04°R905.7, R905.8Shorter exposure below 4/12
Slate4/1218.43°R905.6.2—

The multiplier gives the area to cover, not the amount to buy. Add waste on top: about 10% for simple gable roofs and 15% or more for hips and valleys. The waste factor calculator walks through it.

Sources

Frequently asked questions

How many degrees is a 2/12 pitch?

A 2/12 pitch is 9.46 degrees. Its pitch multiplier is 1.0138, so it adds only about 1.4% to the footprint area.

How many degrees is a 3/12 pitch?

A 3/12 pitch is 14.04 degrees, with a multiplier of 1.0308 (about 3.1% added area).

What is 20/12 roof pitch in degrees?

A 20/12 pitch is 59.04 degrees. Its multiplier is 1.9437, so the roof surface is nearly double the footprint.

What is the pitch factor for a 6/12 roof?

The pitch factor (multiplier) for 6/12 is 1.118. Multiply the flat area by 1.118, which adds about 11.8%.

Do I use the pitch multiplier on a hip roof?

Yes. If every plane has the same pitch, the sloped area of a hip roof is the footprint times the same multiplier as a gable roof. Hips change the waste and the ridge-cap footage, not the area formula.

Does the multiplier include waste?

No. It gives the true surface area. Add a waste allowance separately when ordering material.

How do I find the footprint?

Measure the outside of the walls and add the overhang on every side, or measure the drip edge-to-drip edge dimensions from the ground. Building plans list the roof outline too.